2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-2

MITSUBISHI ELECTRIC 2033C SERIES UPS

3.3 Installation Procedure

A) Note the load tolerance of the floor

Refer to Table 3.2 for list of UPS weights:

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

7.5

10

15

20

30

40

50

Weight (lb.)

562

562

816

816

1235

1082

1082

Note: 40kVA and 50kVA UPS have batteries external to module cabinet

Please refer to the remote battery supply installation manual.

B) Minimum clearance required for ventilation

Right side

1.0" (25 mm) (not required when sidecars are used)

Left side

1.0" (25 mm) (not required when sidecars are used)

Back side

7.8" (200 mm)

Top side

39.4" (1000 mm)

C) Space requirement for routine maintenance

Allow for the following space at the time of installation.

Front

39.4" (1000 mm)

Sides

1.0" (25 mm)

Rear

7.8" (200 mm)

D)

Battery

Please refer to the following when installing and maintaining batteries:

1.

Servicing of batteries should be performed or supervised by personnel

knowledgeable of batteries and the required precautions. Keep unauthorized

personnel away from batteries.

2.

When installing or replacing batteries, install or replace with the same number

and type per Table 3.3

TABLE 3.3 Type and number of battery

Type

Manufacturer

Number

7.5kVA,10kVA PM12-7.2

NP7-12

Power Battery Inc.
Yuasa Corp.

30

15kVA,20kVA PM12-18

NP18-12B

Power Battery Inc.
Yuasa Corp.

30

30kVA PM12-18

NP18-12B
NP18-12BFR

Power Battery Inc.
Yuasa Corp.
Yuasa Corp.

30

40kVA,50kVA