6

6..3

3..7

7 G

Ge

en

ne

erra

all T

Tiim

me

err S

Se

ettu

up

p

User may edit all general purpose timers. Generally, global timers

affect engine operation. They also help define an event.

a

a)) B1: All event types can be associated with, and locked out

by, a Bx timer. B1 is the first global timer used for delaying

an event condition detection. The timer starts in a running

State (10 – 13) depending on which have been marked ‘In

Use’. B1 is also known as the “Lockout Timer.”

b

b)) B2: The second global timer used for delaying an event

condition detection. B2 is also known as a secondary

“Lockout Timer.”

c

c)) C: The delay allowing a clear reading before beginning

testing for the arming of Class C events. The default and

typical time for most applications is 2 seconds.

d

d)) S: Users have up to five (5) options to assign additional

special global timers to signals. The Sx timers begin con-

currently with the Bx timers.

e

e)) No Flow: The global delay used for delaying the triggering of

a No Flow event. This global no flow timer is enabled after

B1 expires, and begins timing after any of the no flow transi-

tion times configured in the digital input dialog expires.

ff)) Test: Time given to allow for maintenance testing of end

devices without triggering a fault or shutdown condition.

The timer initiates when switched to test mode.

g

g)) Ignition Off Delay: Time delay before the assigned ignition

output turns off. This is typically used to burn remaining

fuel vapors after the fuel valve is turned off.

h

h)) Ignition On Delay: Time delay before the assigned ignition

output turns on. This is typically used to delay ignition

until engine crank rollover can occur.

ii)) Fuel On Delay: Time delay before the assigned fuel valve

output is turns on. This is typically used to delay fuel until

ignition has been turned on.

TM

C

C

C

General Timer Setup Screen

___________________________________

GENERAL TIMER SETUP

B1 TIMER
B2 TIMER
C TIMER
S1 TIMER

S2 TIMER

(0 - 999) 00060

▼▲ ENTER-EDIT