a)) Assign value for Warmup RPM.

b

b)) Assign value for Wait to Load RPM.

c

c)) Assign value for Run Loaded RPM.

d

d)) Assign value for Cooldown RPM.

6

6..3

3..1

13

3 M

Miis

sc

ce

elllla

an

ne

eo

ou

us

s S

Se

ettu

up

p

User can access and edit the miscellaneous settings.

a

a)) Crank Attempts: Define a value for number of crank

attempts after which an over-crank sequence will be trig-

gered in the Event logic.

b

b)) Controller Slave Address: Provide the value for the Modbus

Address Port. The factory default is 1.

c

c)) Port 1 Mode: Select Communication Port 1 as RS232, or RS485.

d

d)) Port 1 Reply Delay: To ensure sufficient time for the

Modbus reply, assign appropriate time value for Delay

Modbus Reply Port 1.

e

e)) Port 1 Baud Rate: Select appropriate transmission baud rate

ff)) Port 2 Mode: Select Communication Port 2 as RS232, or RS485.

g

g)) Port 2 Reply Delay: To ensure sufficient time for the

Modbus reply, assign appropriate time value for Delay

Modbus Reply Port 2.

h

h)) Port 2 Baud Rate: Select appropriate transmission baud rate

ii)) Flywheel Teeth: Define a value for Flywheel Teeth used to

calculate RPM.

The following cold temperature offset values should only be adjusted by personnel with a full working knowledge of the

Centurion in conjunction with calibrated reference equipment.

jj)) Core Cold Temp Offset: Enter a non-zero Value for Core

Temperature Adjustment (in tenths) to adjust the temperature

readings for all Thermocouple inputs on both the Main I/O Module

(C3-1). Entering a non-zero value will adjust the Cold Junction

Compensation reading used to calculate temperature.

k

k)) Exp Cold Temp Offset: Enter a non-zero Value for

Expansion Board Temperature Adjustment (in tenths) to

adjust the temperature readings for all Thermocouple inputs

on Expansion I/O (C3-2). Entering a non-zero value will

adjust the Cold Junction Compensation reading used to cal-

culate temperature.

ll)) Hour Meter: The user may make hour meter adjustments.

The range is 0 – 65535 hours.

TM

C

C

C

Initial RPM Setup Screen

___________________________________

INITIAL RPM SETUP

WARMUP RPM

00600

WAIT FOR LOAD RPM
RUN LOADED RPM
COOLDOWN RPM

▼▲ ENTER-EDIT

MORE MENUS

___________________________________

___________________________________

TM

C

C

C

Miscellaneous Setup Screen

___________________________________

MISCELLANEOUS SETUP

NUMBER OF CRANK ATTEMPTS

00003

PORT 1 SLAVE ADDRESS
PORT 1 RS432/RS485
PORT 1 RESPONSE DELAY

PORT 1 BAUD RATE

▼▲ ENTER-EDIT