5 general specificationsl, General specificationsl -13 – MITSUBISHI ELECTRIC F940GOT-SWD-E User Manual

Page 41

Advertising
background image

F940GOT-SWD-E/LWD-E

Installation, Wiring and General Specifications 2.

2-13

2.5

General specificationsl

Ambient temperature

During operation: 0 to +50

°

C (0 to +40

°

C when extension interface is used)

During storage: -20 to +60

°

C

Ambient humidity

During operation: 35 to 85%RH (Condensation shall not be allowed.)

Vibration resistance

In accor-
dance with
JIS B3501
and IEC
1131-2

Frequency Acceleration Amplitude

10 times in
each of X,
Y and Z
directions
(for 80
minutes)

When inter-
mittent

10-57Hz

-

0.075mm

vibrations
are applied

57-150Hz

9.8m/s

2

-

When con-
tinuous

10-57Hz

-

0.035mm

vibrations
are applied

57-150Hz

4.9m/s

2

-

Impact resistance

In accordance with JIS B3501 and IEC 1131-2 (147 m/s

2

, three times in

each of X, Y and Z directions)

Noise resistance

By noise simulator whose noise voltage is 1,000 Vp-p, noise width is 1

µ

s and

cycle is 30 to 100 Hz

Withstand voltage

500V AC for 1 minute

Between all power terminals as a whole
and ground terminal

Insulation resistance 500V DC, 5M

or more by megger

Grounding

Class 3 grounding

Operating atmosphere Corrosive gas and much dusts shall not be detected.

Protection structure

IP65F

Advertising
This manual is related to the following products: