OM-480 Page 21

7-2. 240 Volt Duplex Receptacle (Optional)

Ref. 206 029 / 174 408

Y If unit does not have GFCI re-

ceptacles, use GFCI-pro-

tected extension cord.

1

240 V 15 A AC Receptacle

RC1

Receptacle supplies 60 Hz single-

phase power at weld/power speed.

Maximum output is 3 kVA/kW.
2

Circuit Breakers CB1 And

CB2

CB1 and CB2 protect the

receptacles from overload. If CB1

or CB2 opens, the 240 V receptacle

and half of the 120 V receptacle

does not work. 120 volts may still be

present at the 240 V receptacle.

.

If a circuit breaker continues to
open, contact Factory Autho-
rized Service Agent.

Combined output of all receptacles

is 3 kVA/kW. Generator power is

not affected by weld output.
EXAMPLE: If 10 A is drawn from the

240 V receptacle, only 5 A is avail-

able at the 120 V receptacle:
(240 V x 10 A) + (120 V x 5 A) = 3.0

kVA/kW

1

2

1