DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) — page 15

installatiOn

oUtDoor inStallation

Install the generator in a area that is free of debris,

bystanders, and overhead obstructions. Make sure the

generator is on secure level ground so that it cannot slide

or shift around. Also install the generator in a manner so

that the exhaust will not be discharged in the direction of

nearby homes.
The installation site must be relatively free from moisture

and dust. All electrical equipment should be protected from

excessive moisture. Failure to do will result in deterioration

of the insulation and will result in short circuits and

grounding.
Foreign materials such as dust, sand, lint and abrasive

materials have a tendency to cause excessive wear to

engine and alternator parts.

inDoor inStallation

Exhaust gases from diesel engines are extremely

poisonous. Whenever an engine is installed indoors the

exhaust fumes must be vented to the outside. The engine

should be installed at least two feet from any outside wall.

Using an exhaust pipe which is too long or too small can

cause excessive back pressure which will cause the engine

to heat excessively and possibly burn the valves.

moUnting

The generator must be mounted on a solid foundation (such

as concrete) and set firmly on the foundation to isolate

vibration of the generator when it is running. The generator

must set at least 6 inches above the floor or grade level (in

accordance to NFPA 110, Chapter 5-4.1).

DO NOT remove

the metal skids on the bottom of the generator. They are

to resist damage to the bottom of the generator and to

maintain alignment.

CaUtion

Pay close attention to ventilation when operating the

generator inside tunnels and caves. The engine exhaust

contains noxious elements. Engine exhaust must be

routed to a ventilated area.

generator groUnDing

To guard against electrical shock and possible damage to

the equipment, it is important to provide a good

EARTH

ground.
Article 250 (Grounding) of the National Electrical Code

(NEC) provides guide lines for proper grounding and

specifies that the cable ground shall be connected to the

grounding system of the building as close to the point of

cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following

grounding requirements:
1. Use one of the following wire types to connect the

generator to earth ground.
a. Copper - 8 AWG (5.3 mm

2

) or larger.

b. Aluminum - 6 AWG (8.4 mm

2

) or larger.

2. When grounding the generator (Figure 2) connect the

ground cable between the lock washer and the nut on

the generator and tighten the nut fully. Connect the

other end of the ground cable to earth ground.

3. NEC article 250-52(c) specifies that the earth ground rod

should be buried a minimum of 8 ft. into the ground.

NOTICE

When connecting the generator to any buildings

electrical system

alWaYS consult with a licensed

electrician.

NOTICE

This generator has a permanent bonding conductor

between the generator stator windings and the frame.