Generator outputs, Generator output voltages, Voltage selector switch – Multiquip MQ Power Whisperwatt 60HZ Generator DCA150USJ2 User Manual

Page 42: Voltage selector switch locking button, Generator amperage, Gfci receptacle load capability

Advertising
background image

page 42 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11)

generatOr Outputs

generator oUtpUt voltageS

A wide range of voltages are available to supply voltage for

many different applications. Voltages are selected by using

the

voltage selector switch (Figure 14). To obtain some of

the voltages as listed in Table 7 (see below) will require a

fine adjustment using the

voltage regulator (VR) control

knob located on the control panel.

voltage Selector Switch

The voltage selector switch (Figure 14) is located above

the output terminal panel’s Hard Wire Hook-up Panel. It

has been provided for ease of voltage selection.

Figure 14. Voltage Selector Switch

voltage Selector Switch locking Button

The voltage selector switch has a locking button to protect

the generator and load from being switched while the

engine is running. To lock the voltage selector switch, press

and hold the red button located at the bottom of the switch.

CaUtion

never change the position of the voltage selector

switch while the engine is running. alWaYS place

circuit breaker in the

OFF position before selecting

voltage

.

table 7. voltages available

UvWo output

terminal lugs

voltage Selector Switch

3-phase 240/139v position

voltage Selector Switch

3-phase 480/270v position

line-line

208V

220V

240V

416V

440V

480V

line-neutral

120V

127V

139V

240V

254V

277V

voltage Selector Switch Single-phase 240/120v position

line-neutral/
line-line

120V

Line-Neutral

N/A

N/A

240V

Line-Line

N/A

N/A

Generator Amperage

Table 8 shows the

maximum amps the generator can

provide.

DO NOT exceed the maximum amps as listed..

gFCi receptacle load Capability

The load capability of the GFCI receptacles is directly

related to the voltage being supplied at either the output

terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is

available at the GFCI receptacles when the output terminals

and twist lock receptacles are in use. Be careful that your

load does not to exceed the available current capability at

the receptacles.

table 8. generator maximum amps

rated voltage

maximum amps

1Ø 120 Volt

333.3 amps (4 wire)

1Ø 240 Volt

166.7 amps (4 wire)

3Ø 240 Volt

361 amps

3Ø 480 Volt

180 amps

table 9. 1Ø gFCi receptacle load Capacity

KW in Use

twist lock (C6369)

available load

Current (amps)

1Ø 240/120V

GFCI Duplex

5-20R 120V

87.0

0

85.8

5 amps/receptacle

84.6

10 amps/receptacle

83.4

15 amps/receptacle

82.2

20 amps/receptacle

Table 10. 3Ø

gFCi receptacle load Capacity

Kva in Use

(UvWo terminals)

available load

Current (amps)

3Ø 240/480V

GFCI Duplex

5-20R 120V

150

0 amps/receptacle

146

5 amps/receptacle

142

10 amps/receptacle

138

15 amps/receptacle

133

20 amps/receptacle

Advertising