DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) — page 45

Output terMinal panel cOnnectiOns

3Ø-480/277v UvWo terminal output voltages

1. Place the voltage selector switch in the 3Ø 480/277

position as shown in Figure 25.

Figure 25. Voltage Selector Switch

3Ø-480/277V Position

2. Connect the load wires to the UVWO terminals as

shown in Figure 26.

Figure 26. UVWO Terminal Lugs

3Ø-440/254V Connections

3. Turn the voltage regulator knob (Figure 22) clockwise

to increase voltage output, turn counterclockwise

to decrease voltage output. Use voltage regulator

adjustment knob whenever fine tuning of the output

voltage is required.

1Ø-240/120v UvWo terminal output voltages

1. Place the voltage selector switch in the 1Ø 240/120

position as shown in Figure 27.

Figure 27. Voltage Selector Switch

1Ø-240/120V Position

2. Connect the load wires to the UVWO terminals as

shown in Figure 28.

Figure 28. UVWO Terminal Lugs

1Ø-200/100V Connections

3. Turn the voltage regulator knob (Table 7Figure 22)

clockwise to increase voltage output, turn

counterclockwise to decrease voltage output. Use

voltage regulator adjustment knob whenever fine tuning

of the output voltage is required.

NOTICE

alWaYS make sure that the connections to the UVWO

terminals are

secure and tight. The possibility of arcing

exists, that could cause a fire.