page 52 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11)

generatOr shut-dOWn prOcedures

normal ShUtDoWn proCeDUre

To shutdown the generator, use the following procedure:
1. Place both the

main, gFCi and loaD circuit breakers

as shown in Figure 54 to the

OFF position..

Figure 54. Main, GFCI and Load

Circuit Breakers Off

2. Place the engine speed switch (Figure 55) in the “

loW

(down) position..

Figure 55. Engine Switch (Normal)

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

4. Place the

mpeC Control Switch (Figure 56) to the

oFF/reSet position.

Figure 56. MPEC Control Switch (Off/Reset)

5. Verify that

all status LEDs on the MPEC display are

OFF (not lit).

6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening

of components that may have occurred during

operation.

emergenCY ShUtDoWn proCeDUre

1. Place the

mpeC Control Switch (Figure 56) in the

oFF/reSet position.

12. The

tachometer gauge (Figure 51) will indicate the

speed of the engine when the generator is operating.

Under normal operating conditions this speed is

approximately 1800 RPM’s.

Figure 51. Engine Tachometer Gauge

13. Place the

main, gFCi, and aux. circuit breakers in the

ON position (Figure 52).

Figure 52. Main, Aux. and GFCI

Circuit Breakers (ON)

14. Observe the generator’s ammeter (Figure 53) and

verify it reads the anticipated amount of current with

respect to the load. The ammeter will only display a

current reading if a load is in use.

Figure 53. Ammeter (Load)

15. The generator will run until manually stopped or an

abnormal condition occurs.

Warning

never stop the engine suddenly except in an

emergency.