5-8. Selecting Weld Cable Sizes*

Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit

Not Exceeding***

100 ft (30 m) or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Weld Output

Terminals

Y Stop engine before

connecting to weld out-

put terminals.

Y Do not use worn, dam-

aged, undersized, or

poorly spliced cables.

Welding

Amperes

10 − 60%

Duty

Cycle

60 − 100%

Duty

Cycle

10 − 100% Duty Cycle

100

4 (20)

4 (20)

4 (20)

3 (30)

2 (35)

1 (50)

1/0 (60)

1/0 (60)

150

3 (30)

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

3/0 (95)

200

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 4/0 (120)

250

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 2/0

(2x70)

300

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 3/0

(2x95)

350

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

400

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

2 ea. 4/0

(2x120)

*

This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.

**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.

( ) = mm

2

for metric use

S-0007-F

***For distances longer than those shown in this guide, call a factory applications representative at 920-735-4505.

5-9. Remote Receptacle Information

Engine runs at weld/power speed whenever a device connected to the remote
receptacle is running.

NOTE

Socket*

Socket Information

24 VOLTS AC

A

24 volts ac.

A

J

24 VOLTS AC

B

Contact closure to A completes 24 volt ac contac-

tor control circuit and keeps engine at Run speed

in all modes. Protected by circuit breaker CB5.

A

J

B

K

I

115 VOLTS AC

I

115 volts ac. Protected by fuse F2.

B

C L N

H

D M

G

115 VOLTS AC

J

Contact closure to I completes 115 volts ac

contactor control circuit.

D M

G

E

F

REMOTE

C

0 to +10 volts dc output to remote control in Stick

and TIG modes. +10 volts dc output to remote

control in Wire mode.

REMOTE

OUTPUT

CONTROL

D

Remote control circuit common.

CONTROL

E

0 to +10 volts dc input command signal from

remote control. Voltage is dependent on front pan-

el Voltage/Amperage control setting.

GND

G

Circuit common for 24 and 115 volts ac circuits.

GND

K

Chassis common.

*The remaining sockets are not used.

Advertising
This manual is related to the following products: