Power load capacity, Chapter 55. xseries rack power configurator – IBM SCOD-3ZVQ5W User Manual

Page 489

Advertising
background image

Chapter 55. xSeries rack power configurator

481

Country-specific considerations: USA, Canada, parts of Latin America,
Taiwan

Power Load Capacity

Part

Number

Plug Type

Source Circuit
(single phase 50/60Hz)

PDU Output
(single phase 50/60Hz)

32P1761

NEMA L5-15

P

100-127Vac,

15a

six 100-127Vac, NEMA 5-15R
receptacles, shared

12a

NEMA L5-20P

100-127Vac, 20a

seven 100-127Vac, shared 15a

NEMA L6-20P

200-240Vac, 20a

seven 200-240Vac, shared 15a

32P1736

Part
Number

Plug Type

Source Circuit (50/60Hz)

PDU Output
(single phase 50/60Hz)

32P1751 NEMA L5-30P

100-127Vac, 30a,
single-phase

three 100-127Vac, 20a each, shared

24a

32P1766 NEMA L6-30P

208Vac, 30a, single-phase
line-to-line with ground

three 208Vac, 20a each, share

d 24a

32P1767 IEC 309-2P+G

208Vac, 60a, single-phase
line-to-line with ground

three 208Vac, 20a each, shared
48a

Part
Number

Plug Type

Source Circuit (50/60Hz)

PDU Output
(single phase 50/60Hz)

73P5855 IEC 309 2P+G

208Vac, 60a, single-phase
dedicated circuit

twelve 208Vac, 16a each, shared
48a

73P5847 IEC 309 3P+G

208Vac, 60a, three-phase
delta dedicated circuit

twelve 208Vac, 16a each, shared
28a per four outlet phase group

Rack PDUs

Front-end PDUs

High Density PDUs

Enterprise PDUs

Part
Number

Plug Type

Source Circuit (50/60Hz)

PDU Output
(single phase 50/60Hz)

26K42

46 NEMA L6-30P

208Vac, 30a, single-phase
dedicated circuit

twelve 208Vac, 10a each, shared
24a

26K4242 IEC 309 2P+G

208Vac, 60a, single-phase
dedicated circuit

twelve 208Vac, 10a each, shared
48a

26K4244 IEC 309 3P+G

208Vac, 60a, three-phase
delta dedicated circuit

twelve 208Vac, 10a each, shared
28a per four outlet phase group

26K4256 IEC 309 2P+G

208Vac, 60a, single-phase
dedicated circuit

six 208Vac, 16a each, shared 48a

26K4258 IEC 309 3P+G

208Vac, 60a, three-phase
delta dedicated circuit

six 208Vac, 16a each, shared 28a
per two outlet phase group

(2) Line Cords: Rack PDU

(5) Line Cords: Front-end
PDU

Power Cables:

(1) Device to Rack PDU or Enterprise C13 PDU power cable

IEC C13 to C14, 10/15a cable
typical: 36L8886 (2.8m)
requirement: C14 plug, long enough to reach
available option: 94G7448 (14ft)

(2) Rack PDU to wall line cord

IEC C19 to country-specific connector, 16/20a, 14ft (4.3m)

(3) Rack PDU to UPS power cable

IEC C19 to C20, 16/20a
00N7700 (2m)
provided with 37L6861 APC SU-5000RMB

(4) Rack PDU to Front-end PDU power cable

IEC C19 to C20, 16/20a
00N7698 (1m) provided with the NetBAY Front-end PDUs
00N7700 (2m) provided with the DPI Front-end PDUs

(5) Front-end PDU to wall line cord

hardwired to country-specific connector, 30/32a, 60/63a, 8.2ft

(2.5m)

(7) Device to High Density PDU power cable

IEC C19 to C20, 16/20a, 2.5m

(8) Enterprise PDU to wall line cord

hardwired or pluggable to country-specific connector, 30/60a, 14ft

(4.3m)

(9) High Density PDU to wall line cord

hardwired or plugugable to country-specific connector, 60a, 8.2ft

(2.5m)

(10) Device to FE-, E-, or HD-PDU power cable

IEC C13 to C20, 10/15a cable
option: 23K4809 9ft (2.8m)

(9) Line Cords:High Density PDU

(8) Line Cords:Enterprise PDU

Advertising