Appendix C. UPS runtime estimate (minutes)

Steps to determine UPS runtimes and suitable UPS for desired configurations:

1.

Using the 'Power Load Data' table, sum the load (watts) of all devices in the configuration. Use either
Maximum Load for minimum runtimes, or Typical Load for typical runtimes.

2.

Using the 'Runtimes' table, locate the configuration's total load calculated in step 1.

3.

Select the most appropriate UPS model to achieve the desired runtime.

Note:

If the configuration's total load is greater than the entries in the 'Runtimes' table, split the load across
two or more UPS units.


Table 143. Power Load Data

Server

Number of Power Cords (Std/Max)

Watts Load

(Typical/Max)

1

xSeries 206m

2

2/2

246/352

xSeries 226 (single power supply)

2

1/1

495/707

xSeries 226 (redundant power supplies)

2

2/2

480/685

xSeries 236

2

1/2

625/893

xSeries 260 (two power supplies)

2

2/3

679/970

xSeries 260 (three power supplies)

2

2/3

1288/1840

xSeries 306m

2

1/1

350/500

xSeries 306

2

1/1

300/430

xSeries 336

2

1/2

385/550

xSeries 346

2

1/2

581/830

System x3850 and xSeries 366

2

1/2

1103/1575

System x3950 and xSeries 460

2

2/2

1103/1575

eServer 326m

2

1/1

280/400

x3400 entry

2

1/1

463/662

x3550

2

1/2

490/700

x3650

2

1/2

679/970

x3800 (two power supplies)

2

2/3

679/970

x3800 (three power supplies)

2

2/3

1288/1840

x3850

2

2/2

1103/1575

x3950

2

2/2

1103/1575

BladeCenter (two 2000W power supplies)

2, 3

2/4

1855/2650

BladeCenter (four 2000W power supplies)

2, 3

4/4

3710/5300

BladeCenter H (two 2900W power supplies)

2, 3

2/2

3325/4750

BladeCenter H (four 2900W power supplies)

2, 3

4/4

6650/9500

Other Devices

EXP400 Storage Expansion Unit (17331RU)

2

2/2

310/440