Appendix C. UPS runtime estimate (minutes)

513

Notes:

1.

Data provided by APC.

Table 149. IBM UPS7500XHV, 10000XHV Runtimes

1

Number of Battery Packs

+0

+1

+2

+4

Total Load (Watts)

Runtime

(Hours/Minutes)

Runtime

(Hours/Minutes)

Runtime

(Hours/Minutes)

Runtime

(Hours/Minutes)

200

4/6

7/36

11/54

20/54

300

3/6

5/48

9/6

16/0

400

2/30

4/36

7/18

12/48

500

2/6

3/54

6/6

10/42

600

1/48

3/18

5/12

9/12

700

1/30

2/54

4/30

8/0

800

1/18

2/30

4/0

7/0

900

1/12

2/18

3/36

6/12

1000

1/6

2/0

3/12

5/42

1200

55

1/42

2/42

4/48

1400

47

1/30

2/18

4/6

1600

41

1/12

2/0

3/36

1800

36

1/6

1/48

3/12

2000

32

1/0

1/36

2/54

3000

19

39

1/0

1/48

4000

13

28

46

1/18

5000

10

21

35

1/0

6000

7

16

28

52

7000

5

13

23

44

8000

4

11

20

37

Note:

UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts.