Appendix C. UPS runtime estimate (minutes)
513
Notes:
1.
Data provided by APC.
Table 149. IBM UPS7500XHV, 10000XHV Runtimes
1
Number of Battery Packs
+0
+1
+2
+4
Total Load (Watts)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
200
4/6
7/36
11/54
20/54
300
3/6
5/48
9/6
16/0
400
2/30
4/36
7/18
12/48
500
2/6
3/54
6/6
10/42
600
1/48
3/18
5/12
9/12
700
1/30
2/54
4/30
8/0
800
1/18
2/30
4/0
7/0
900
1/12
2/18
3/36
6/12
1000
1/6
2/0
3/12
5/42
1200
55
1/42
2/42
4/48
1400
47
1/30
2/18
4/6
1600
41
1/12
2/0
3/36
1800
36
1/6
1/48
3/12
2000
32
1/0
1/36
2/54
3000
19
39
1/0
1/48
4000
13
28
46
1/18
5000
10
21
35
1/0
6000
7
16
28
52
7000
5
13
23
44
8000
4
11
20
37
Note:
UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts.