Table 147. IBM UPS3000HV Runtimes
1
Number of Battery Packs
+0
+1
+2
+3
+4
Total Load
(Watts)
Runtime
(Hours / Minutes)
Runtime
(Hours/ Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
200
1/3
4/38
9/5
12/48
16/42
300
55
4/5
8/0
11/16
14/42
400
48
3/33
6/59
9/59
12/50
500
42
3/6
6/4
8/33
11/10
600
36
2/38
5/10
7/17
9/30
700
31
2/14
4/23
6/11
8/4
800
26
1/56
3/48
5/22
7/0
900
23
1/40
3/16
4/36
6/0
1000
19
1/23
2/44
3/51
5/2
1100
16
1/12
2/22
3/20
4/22
1200
14
1/3
2/4
2/54
3/48
1300
12
55
1/48
2/33
3/20
1400
10
47
1/32
2/10
2/50
1500
9
45
1/28
2/4
2/42
1600
9
41
1/20
1/53
2/28
1700
8
40
1/18
1/50
2/24
1800
8
40
1/18
1/50
2/24
1900
7
35
1/8
1/36
2/6
2000
7
35
1/8
1/36
2/6
2100
7
33
1/5
1/32
2/0
2200
6
30
58
1/22
1/48
2300
6
30
58
1/22
1/48
2400
6
30
58
1/22
1/48
2500
6
26
51
1/12
1/34
2600
5
25
49
1/9
1/30
2700
5
25
49
1/9
1/30