IBM SCOD-3ZVQ5W User Manual

Page 519

Advertising
background image

Appendix C. UPS runtime estimate (minutes)

511


Notes:
1.

Data provided by Eaton.

Table 147. IBM UPS3000HV Runtimes

1

Number of Battery Packs

+0

+1

+2

+3

+4

Total Load

(Watts)

Runtime

(Hours / Minutes)

Runtime

(Hours/ Minutes)

Runtime

(Hours / Minutes)

Runtime

(Hours / Minutes)

Runtime

(Hours / Minutes)

200

1/3

4/38

9/5

12/48

16/42

300

55

4/5

8/0

11/16

14/42

400

48

3/33

6/59

9/59

12/50

500

42

3/6

6/4

8/33

11/10

600

36

2/38

5/10

7/17

9/30

700

31

2/14

4/23

6/11

8/4

800

26

1/56

3/48

5/22

7/0

900

23

1/40

3/16

4/36

6/0

1000

19

1/23

2/44

3/51

5/2

1100

16

1/12

2/22

3/20

4/22

1200

14

1/3

2/4

2/54

3/48

1300

12

55

1/48

2/33

3/20

1400

10

47

1/32

2/10

2/50

1500

9

45

1/28

2/4

2/42

1600

9

41

1/20

1/53

2/28

1700

8

40

1/18

1/50

2/24

1800

8

40

1/18

1/50

2/24

1900

7

35

1/8

1/36

2/6

2000

7

35

1/8

1/36

2/6

2100

7

33

1/5

1/32

2/0

2200

6

30

58

1/22

1/48

2300

6

30

58

1/22

1/48

2400

6

30

58

1/22

1/48

2500

6

26

51

1/12

1/34

2600

5

25

49

1/9

1/30

2700

5

25

49

1/9

1/30

Advertising