Sun Microsystems Netra 120 User Manual

Page 68

Advertising
background image

5-4

Sun Fire V120 and Netra 120 Server User’s Guide • December 2001

2. Loosely screw the two parts of the slide mounts together, using the M4 nuts

supplied.

3. Measure the distance between the front and back posts of your rack.

4. Adjust the slide mounts so that the distance between the front and back mounting

ears is approximately the distance between the front and back posts of the rack.

5. Move the brackets so that the studs are in suitable slots, and tighten the nuts.

6. Fasten the mounting slides to the rack, using the screws supplied.

For the Sun StorEdge 72-inch rack, refer to

FIGURE 5-4

and

FIGURE 5-5

. Leave the

screws slightly loose to allow adjustment when you slide the server into the rack.

For a standard 19-inch rack, refer to

FIGURE 5-6

. Leave the screws slightly loose to

allow adjustment when you slide the server into the rack.