1 operating power limits and ranges, Operating power limits and ranges – Sun Microsystems Netra 120 User Manual

Page 36

Advertising
background image

2-2

Sun Fire V120 and Netra 120 Server User’s Guide • December 2001

2.1

Operating Power Limits and Ranges

The table below gives operating and power information for the Sun Fire V120 and
Netra 120 servers.

*

For both servers, the in-rush current decays to the normal operating current in less than

200 milliseconds. The in-rush decaying peaks last for less than 3 milliseconds in each half
cycle.

Note –

The figures for the maximum operating current are provided to help you

specify the fusing and cabling you need to deliver power to your equipment.
However, these figures represent “worst-case” scenarios. Such occurrences are
unlikely in a real installation.

TABLE 2-1

Operating Power Limits and Ranges for Sun Fire V120 and Netra 120 Servers

Description

Sun Fire V120 Server (AC power)

Netra 120 Server (DC power)

Maximum operating
current

2A @ 90 VAC

4A @

40 VDC

Maximum in-rush
current (cold start)

20A peak upon a restart
performed 60 seconds or more
after the removal of AC power

20A peak upon a restart
performed 60 seconds or more
after the removal of DC power

Maximum in-rush
current (warm start)

40A peak upon a restart
performed less than 60 seconds
but more than 200 milliseconds
after the removal of AC power

40A peak upon a restart
performed less than 60 seconds
but more than 200 milliseconds
after the removal of DC power

Maximum in-rush
current (hot start)

100A peak upon a restart
performed less than 200
milliseconds after the removal
of AC power

100A peak upon a restart
performed less than 200
milliseconds after the removal
of DC power

Operating input
voltage range

90-264 V

rms

40 to

75 VDC

Voltage frequency
range

47-63 Hz

DC

Power factor

0.8 to 1.0

Not applicable

BTU rating

550 BTU

550 BTU