5-1

Turn "OFF" the power supply to the JW20/JW20H/JW30H.

Set the mode switch, the termination resistance switch, and the shield ground switch on

the rear side of the JW-21MN.
(See page 11-2 to 11-4 for settings)

- The JW-21MN cannot be installed on the expansion rack panel.
- Number of installations of the JW-21MN on the same JW20/JW20H/JW30H basic rack panel should

be within 7 in total including other option module (including JW-21MN). Installation of more than seven
modules of the JW-21MN will not allow the JW20/JW20H/JW30H to function.

- Make sure to tighten the module retention screws securely. Looseness of the screws may cause

malfunctions.

Chapter 5: Installation

Installation procedure

Hang the module retention rib of the JW-21MN on the retention rib insertion hole of the JW20/

JW20H/JW30H's basic rack panel, and press in the JW-21MN. Then tighten the module retention
screws at the top of the JW-21MN module using a Phillips screwdriver.

Remarks

MODE

ON
OFF

LT

LG

ON
OFF

Applicable screwdriver

(Rear view of the JW-21MN)

Mode switch

Termination
resistance switch

Shield ground switch

(Installation example)

Module retention rib insertion hole

JW-21MN

Power supply
module

JW-21MN

Partition plate or control panel

Basic rack panel

Module insertion guide

Phillips
screwdriver

Basic rack panel

Module retention screw

Ventilation hole

Module retention rib