Sharp JW-21MN User Manual

Page 70

Advertising
background image

11-17

From the previous page

Set top address of register link area on slave station 01 to 77

(8)

(at standard function)/number

of offset bytes (at save memory function)

Set in parameter addresses 004404 to 004777

(8)

. These top addresses should not overlap the

resister link area, flag area, or any area used by other option module.

Slave

station

01

Lower

Upper

File number

·

In case of standard function, set top address by file address

(8)

.

In case of save memory function, set number of offset bytes.

004404

(8)

004405

(8)

004406

(8)

004407

(8)

00

(H)

: The top address is the same address of the master station

regardless of the values set at of 004404 to 004405

(8)

.

80

(H)

: The top address is different from the address of the master

station (Offset is valid).
For the save memory function, set in 80

(H)

.

Slave

station

77

(8)

Lower

Upper

File number

·

004774

(8)

004775

(8)

004776

(8)

004777

(8)

00

(H)

80

(H)

- In case of setting 0 (the top address is 0440, the same as the address of the master station) in

parameter addresses 004404 to 004407

(8)

(slave station 01) and the offset byte number 8 and

"offset valid" on the parameter address 004410 to 004413

(8)

(slave station 02). (Example for 11-10)

Slave

station

01

Write 0 in parameter 004004 to 004007

(8)

(same as

master station).

Write 00010

(D)

(offset 8) in parameter

addresses 004410 to 004411

(8)

.

Write 000

(H)

(file 0) in parameter address 004412

(8)

.

Write 80

(H)

(offset valid) in parameter address 004413

(8)

.

Slave

station

02

0000

(H)

00

(H)

00

(H)

Screen display of JW-14PG

004404

(8)

004405

(8)

004406

(8)

004407

(8)

Slave

station

01

00008

(D)

80

(H)

00

(H)

Slave

station

02

004410

(8)

004411

(8)

004412

(8)

004413

(8)

Set the number of sending bytes of the master station relay link [DCM (decimal), word]

Set in parameter addresses 005000 to 005001

(8)

.

005000

(8)

005001

(8)

Upper

Lower

These top addresses should not overlap the resister link area, or the flag area, or exceed the setting

range (0 to 256 bytes for each station, 256 bytes for all stations in total).

- In case of setting 8 bytes (Example for page 11-10)

Display the contents of parameter addresses 005000 to 005001

(8)

Write 00008

(D)

after converting to decimal.

Screen display of JW-14PG

00008

(D)

005000

(8)

005001

(8)

To the next page

04011 HEX 00
04012 HEX 00
I PARAM.
>04013 HEX 80

04774 D 00000
04776 D 00000
I PARAM.
>05000 D 00008

(Word display)

(Word display)

(Word display)

(Byte display)