3 cable wiring procedure in control panel, 3 cable wiring procedure in control panel -2 – Sharp JW-21MN User Manual

Page 23

Advertising
background image

7-2

(1) Fixing of the cable

In order not to put any force on the cable and the
JW-21MN, fasten the cable to an line nearby input of
a control panel or a "T" branch point to the JW-
21MN using saddles etc.

(2) Extra length of cable

Provide an extra length of the cable of 2 to 3 m
inside a control panel for easier processing of the
cable end and easier wiring when changing module
positions.

(3) Connection to the JW-21MN

The connector to the JW-21MN should be turned
right to secure locking, not merely inserted.

(4) Insulation cover

When the connector touches with a high voltage
section or external enclosures, communication
errors may occur. Make sure to install an insulation
cover.

(5) Grounding of power supply module (JW-22PU/31PU)

Make sure to use a class-3 grounding to connect the GND terminal of the power supply module.
- If the power supply module is not grounded, the JW-21MN cannot conduct with the ground after

turning "ON" the shield ground switch.

7-3 Cable wiring procedure in control panel

Saddle

Saddle

JW-21MN

Communication cable

connection connector

"L" jacket

(insulation cover)

"T" jacket

(insulation cover)

POWER
INPUT
100-120VAC

SHORT

GND

HALT
OUTPUT

100-120VAC

(24VDC)
1A

GND (ground) terminal

Halt output terminal

Class-3
grounding

Power input terminal for
85 to 132 VAC

When using a JW-31PU AC power supply module

Advertising