Application 2561 VAV Cooling or Heating

Overview

In Application 2561, the controller modulates the supply air damper of the terminal box for
cooling and heating. In order for it to work properly, the central air-handling unit must provide
cool supply air in cooling mode and warm air in heating mode. See Figure 6.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2561CDR1

Air

Velocity

Sensor

Supply Air

Damper

SAFETIES

BY

OTHERS

3 4 5 6

C

Wall Switch (Opt.)

N O

Spare DO or
Autozero Module (Opt.)

Spare DOs

"COMMON" Termination for all DOs

Duct Temp Sensor
(10K ohm thermistor - Opt.)

Supply Air

3 to 5 Straight Duct Diameters

required for proper sensor reading

Hi/Lo Tubing

Connections

RTS

FLN

Figure 6. Application 2561 Control Drawing.