Overview, Fan operation, Applications – Siemens BACNET 125-5037 User Manual

Page 28: The fan turns on when heating is required, 18 siemens building technologies, inc

Advertising
background image

Applications

18

Siemens Building Technologies, Inc.

Application 2567 VAV Parallel Fan Powered with Hot
Water Reheat

Overview

In Application 2567, the controller modulates the supply air damper of the terminal box to
provide for cooling and modulates a hot water valve for heating. When in heating, the
terminal box either maintains minimum airflow or modulates the supply air damper. The
terminal box also has a parallel fan that re-circulates the room air. In order for the terminal
box to work properly, the central air handling unit must provide supply air. See Figure 14.

Fan Operation

The fan turns on when heating is required.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2567CDR1

Air

Velocity

Sensor

SAFETIES

BY

OTHERS

6

5

4

3

C

Wall Switch (Opt.)

"COMMON" Termination for all DOs

10K ohm Thermistor
or Spare DI

Hi/Lo Tubing

Connections

RTS

FLN

NO

Supply

Air Damper

Supply Air

Recirculated

Plenum Air

Recirculated

Air Damper

3 to 5 Straight Duct Diameters

required for proper sensor reading

Valve

Actuator

Spare DO

Fan

Figure 14. Application 2567 Control Drawing.