Overview, Fan operation, Siemens bacnet vav actuator owner’s manual – Siemens BACNET 125-5037 User Manual

Page 27: The fan turns on when heating is required, Siemens building technologies, inc. 17

Advertising
background image

Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

17

Application 2566 VAV Parallel Fan Powered with
Electric Reheat

Overview

In Application 2566, the controller modulates the supply air damper of the terminal box for
cooling and controls stages of electric reheat for heating. When in heating, the terminal box
either maintains minimum airflow or modulates the supply air damper. The terminal box also
has a parallel fan, which re-circulates the room air. In order for the terminal box to work
properly, the central air handling unit must provide supply air. See Figure 13.

Fan Operation

The fan turns on when heating is required.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2566CDR1

Air

Velocity

Sensor

SAFETIES

BY

OTHERS

6

5

4

3

C

Wall Switch (Opt.)

"COMMON" Termination for all DOs

10K ohm Thermistor
or Spare DI

Hi/Lo Tubing

Connections

RTS

FLN

NO

Supply

Air Damper

Supply Air

Recirculated

Plenum Air

Recirculated

Air Damper

3 to 5 Straight Duct Diameters

required for proper sensor reading

Fan

Elec Heat

Stage 1

Electric Heat

Stage 2

Electric Heat

Stage 3

Figure 13. Application 2566 Control Drawing.

Advertising