Applications, 12 siemens building technologies, inc – Siemens BACNET 125-5037 User Manual

Page 22

Advertising
background image

Applications

12

Siemens Building Technologies, Inc.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2562ACDR1

Air

Velocity

Sensor

Supply Air

Damper

SAFETIES

BY

OTHERS

3 4 5 6

C

Wall Switch (Opt.)

Spare DO or
Autozero Module (Opt.)

"COMMON" Termination for all DOs

Hi/Lo Tubing

Connections

RTS

FLN

NO

Elec Heat

Stage 3

Electric Heat

Stage 2

Electric Heat

Stage 1

10K ohm Thermistor
or Spare DI

Supply Air

3 to 5 Straight Duct Diameters

required for proper sensor reading

Figure 7. Application 2562 Control Drawing (Electric Heat).

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2562BCDR1

Air

Velocity

Sensor

Supply Air

Damper

SAFETIES

BY

OTHERS

3 4 5 6

C

Wall Switch (Opt.)

Spare DO or
Autozero Module (Opt.)

"COMMON" Termination for all DOs

Hi/Lo Tubing

Connections

RTS

FLN

NO

2-Position

Valve

Spare DOs

10K ohm Thermistor
or Spare DI

Supply Air

3 to 5 Straight Duct Diameters

required for proper sensor reading

Figure 8. Application 2562 Control Diagram (Baseboard Radiation).