Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

21

Descriptor Address

1

Application Description

RM STPT MAX

12

All except 2597

The maximum temperature setpoint in degrees that
the controller can use from the setpoint dial. This
overrides any temperature setpoint from the
setpoint dial that falls above this maximum.

RM STPT DIAL

{13}

2

All

The temperature setpoint in degrees from the room
temperature sensor (not available on all
temperature sensor models). This setpoint will be
used for control in day mode (heating or cooling)
when enabled by STPT DIAL.

STPT DIAL

14

All except 2597

YES indicates that there is a room setpoint dial on
the room temperature sensor and it should be used
as the temperature setpoint for control in
day/occupied mode. NO indicates that the
appropriate preset setpoint will be used as the
temperature setpoint for control in day/occupied
heating or cooling mode. Valid input: YES or NO.

AUX TEMP

{15}

All except 2561

Actual reading from a 10K

Ω thermistor connected

to the controller's Al 3 input. When a thermistor is
connected at Al 3, DI 3 is not available. See DI 3.

SUPPLY TEMP

{15}

2561

Actual reading from a 10K

Ω thermistor connected

to the controller's Al 3 input. The controller uses this
value to determine whether it is in heating or
cooling mode.

FLOW START

16

All except

2560, 2561, 2597

Determines how the damper modulation will be
sequenced while in heating mode. When HTG
LOOPOUT is above this value, then FLOW STPT
starts to increase.

FLOW END

17

All except

2560, 2561, 2597

Determines how the damper modulation will be
sequenced while in heating mode. When HTG
LOOPOUT is below this value, then FLOW STPT
starts to decrease.

WALL SWITCH

18

All

YES indicates that the controller is to monitor the
status of a wall switch that is connected to DI 2. NO
indicates that the controller will not monitor the
status of a wall switch, even if one is connected.
Valid input: YES or NO.

DI OVRD SW

{19}

2

All

Actual indication of the status of the override switch
(not physically available on all temperature sensor
models) at the room temperature sensor. ON
indicates that the switch is being pressed. OFF
indicates that the switch is released.
Valid input: ON or OFF.

OVRD TIME

20

All except

2597

The amount of time in hours that the controller will
operate in day/occupied mode when the override
switch is pressed while the controller is in
night/unoccupied mode.