Application 2563 vav with hot water reheat, Overview, Siemens bacnet vav actuator owner’s manual – Siemens BACNET 125-5037 User Manual

Page 23: Siemens building technologies, inc. 13

Advertising
background image

Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

13

Application 2563 VAV with Hot Water Reheat

Overview

In Application 2563, the controller modulates the supply air damper of the terminal box for
cooling and modulates a reheat valve (or valves) for heating. When in heating, the terminal
box either maintains minimum airflow or modulates the supply air damper. In order for the
terminal box to work properly, the central air handling unit must provide supply air. See
Figure 9 and Figure 10.

BACnet Actuator

Controller

Modulating

Damper

Actuator

TEC2563ACDR1

Air

Velocity

Sensor

Supply Air

Damper

SAFETIES

BY

OTHERS

3 4 5 6

C

Wall Switch (Opt.)

Spare DO or
Autozero Module (Opt.)

"COMMON" Termination for all DOs

10K ohm Thermistor
or Spare DI

Hi/Lo Tubing

Connections

RTS

FLN

NO

Valve

Actuator

Spare DO

Supply Air

3 to 5 Straight Duct Diameters

required for proper sensor reading

Figure 9. Application 2563 Control Drawing (HW Heat and Spare DO).