Siemens BACNET 125-5037 User Manual

Page 33

Advertising
background image

Siemens BACnet VAV Actuator Owner’s Manual

Siemens Building Technologies, Inc.

23

Descriptor Address

1

Application Description

PARALLEL OFF

30

2566,

2567

When flow rises above this value, the parallel fan
will turn OFF.

CLG FLOW MIN

31

All except 2597

The minimum amount of air in CFM (LPS) to be
supplied to the space in cooling mode.

CLG FLOW MAX

32

All except 2597

The maximum amount of air in CFM (LPS) to be
supplied to the space in cooling mode.

HTG FLOW MIN

33

All except 2560,

2597

The minimum amount of air in CFM (LPS) to be
supplied to the space in heating mode.

HTG FLOW MAX

34

All except 2560,

2597

The maximum amount of air in CFM (LPS) to be
supplied to the space in heating mode.

AIR VOLUME

{

35}

2

All

Actual amount of air in CFM (LPS) currently
passing through the air velocity sensor.

FLOW COEFF

36

All

Calibration factor for the airflow sensor.

MTR3 COMD

{37}

2560, 2561, 2562,

2597

The value to which the Motor 3 actuator is
commanded in percent of full value.

VLV2 COMD

{37}

2563

The value to which the valve 2 actuator is
commanded in percent of full travel for applications
using a second water valve.

MTR3 POS

{38}

2560, 2561, 2562,

2597

The current position of the Motor 3 actuator in
percent of full travel. This value is calculated based
on motor run time.

VLV2 POS

{38}

2563

The current position of Valve 2 in percent of full
travel. This value is calculated based on valve run
time.

MTR3 TIMING

39

All except

2564, 2565, 2566,

2567

The time required for the Motor 3 actuator to travel
from the full closed position to the full open position.

DO 1

{41}

2

All

Digital output 1 controls a 24 Vac load with an ON
or OFF status. If Motor 1 is enabled, DO 1 is
coupled with DO 2 to control an actuator.

DO 2

{42}

All

Digital output 2 controls a 24 Vac load with an ON
or OFF status. If Motor 1 is enabled, DO 2 is
coupled with DO 1 to control an actuator.

DO 3

{43}

All except

2562, 2564, 2566

Digital output 3 controls a 24 Vac load with an ON
or OFF status. If Motor 2 is enabled, DO 3 is
coupled with DO 4 to control an actuator.

HEAT STAGE 1

{43}

2562, 2564, 2566

This point is DO 3 in applications with electric
reheat. This digital output controls the contact for
the first stage of heating and has a status of ON or
OFF.