8-4-2. Outdoor Fan Motor

This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil

resistance, and the following procedure should be used to check the motor.

Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit.

[Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble

[Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating.

(Diagnostic procedure)

* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor

unit controller (3 locations).

(Diagnostic results)

All of the above measured values are normal. Fan motor trouble (Replace the motor.)

Any one of the above measured values is not normal. Outdoor unit controller trouble

(Replace the controller .)

(Reference)

DC motor connector pin arrangement

[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor

unit operates.

(There is trouble in the system that provides feedback of motor rotation speed from the

motor to the outdoor unit controller.)

[Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.

[Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.

(Remedy for symptom 3 to 5)

It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble.

Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.

Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors.

(B) When performing voltage measurement at the outdoor controller connector for (3) in the table

below, the DC motor will trip and voltage output will stop approximately 10 seconds after

operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor

unit power, then, measure the voltage in Test Run mode.

Pin 1: Vm (red)

Pin 2: Not used

Pin 3: Gnd (blue)

Pin 1: Vcc (brown)

Pin 2: PG (white)

Pin 3: Vsp (orange)

Pin

FM1

FM2

Connector No.

(1) Vm-Gnd : Between pin 1 and pin 3 of FM1

(2) Vcc-Gnd : Between pin 1 of FM2 and pin3 of FM1

(3) Vs-Gnd : Between pin 3 of FM2 and pin3 of FM1

Measurement location

DC 280V +/- 10%

DC 15V +/- 10%

Fluctuation between DC 1.8V to 5.7V

Normal value

44