6

Fig. 5e

Fig. 5f

Fig. 5g

2-2-1. Installing the Unit in an Area with High Winds

and in a Snowy Area

In locations with high winds, a wind-proof duct

should be fitted and direct exposure to the wind
should be avoided as much as possible. (Fig. 5e)

In regions with significant snowfall, the outdoor unit

should be provided with a platform and snow-proof
duct. (Fig. 5f)

Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not
provided with a platform and ducting:

a) The outdoor fan may not run and damage to the

unit may occur.

b) There may be no air flow.

c) The tubing may freeze and burst.

d) The condenser pressure may drop because of

strong wind, and the indoor unit may freeze.

2-2-2. Precautions for Installation in a Snowy Area

(1) The platform should be higher than the maximum

snow depth. (Fig. 5g)

(2) The 2 anchoring feet of the outdoor unit should

be used for the platform, and the platform should
be installed beneath the air intake side of outdoor
unit.

(3) The platform foundation must be firm and the unit

must be secured with anchor bolts.

(4) In case of installation on a roof subject to strong

wind, countermeasures must be taken to prevent
the unit from being blown over.

Air discharge

Air discharge

Air discharge

Air
discharge

Outdoor unit

Duct

Platform (foundation)

Air Intake

Air Intake

About 1/2 of the unit height

Higher than the

m

axi

mum

sno

w dept

h

Without snow-
proof ducting
(Low platform)

Without snow-
proof ducting
(High platform)