Table 1-16 Refrigerant Charge Amount at Shipment (for outdoor unit)

DC

CHDX09053

CHDX14053

(oz)

423

458

1-9. System Limitations

Table 1-17 System Limitations

Max. No. allowable connected outdoor units

2

*1

Max. capacity allowable connected outdoor units

307,100 BTU/h (32 hp, 90 kW)

Max. connectable indoor units

40

Max. allowable indoor/outdoor capacity ratio

50 – 130 %

*1: Up to 2 units can be connected if the system has been extended.

1-7. Straight Equivalent Length of Joints

Design the tubing system by referring to the following table for the straight equivalent length of joints.

Table 1-13 Straight Equivalent Length of Joints

Gas tubing size (in. (mm))

1/2"

(12.7)

5/8"

(15.88)

3/4"

(19.05)

7/8"

(22.22)

1"

(25.4)

1-1/8"

(28.58)

1-1/4"

(31.8)

1-1/2"

(38.1)

90

° elbow

1

1.1

1.4

1.6

1.7

1.9

2.3

2.6

45

° elbow

0.8

0.9

1

1.2

1.3

1.4

1.7

1.9

U-shape tube bent (R2-3/8" – 4" (60 – 100))

3

3.4

4.1

4.7

5.1

5.6

6.9

7.8

Trap bend

7.5

9.2

10.5

12.5

14.1

15.4

16.4

14.0

Y-branch distribution joint

Equivalent length conversion not needed.

Ball valve for service

Equivalent length conversion not needed.

Table 1-14 Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material O

Material 1/2H • H

ш1/4" (ш6.35)

t1/32" (0.8)

ш7/8" (ш22.22)

t5/128" (1.0)

ш3/8" (ш9.52)

t1/32" (0.8)

ш1" (ш25.40)

t5/128" (1.0)

ш1/2" (ш12.7)

t1/32" (0.8)

ш1-1/8" (ш28.58)

t5/128" (1.0)

ш5/8" (ш15.88)

t5/128" (1.0)

ш1-1/4" (ш31.75)

t3/64" (1.1)

ш3/4" (ш19.05)

over t5/128" (1.0)

ш1-1/2" (ш38.10)

over t3/64" (1.15)

ш1-5/8" (ш41.28)

over t3/64" (1.20)

* When bending the tubes, use a bending

radius that is at least 4 times the outer

diameter of the tubes.

In addition, take sufficient care to avoid

crushing or damaging the tubes when

bending them.

1-8. Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 1-15 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4" (ш6.35)

0.279

ш3/8" (ш9.52)

0.602

ш1/2" (ш12.7)

1.38

ш5/8" (ш15.88)

1.99

ш3/4" (ш19.05)

2.78

ш7/8" (ш22.22)

3.93

Required amount of charge = (Amount of refrigerant charge per

meter of each size of liquid tube

× its tube length) + (...) + (...)

* Always charge accurately using a scale for weighing.

* If the existing tubing is used, and the amount of on-site additional

refrigerant charge exceeds the value listed below, then change the

size of the tubing to reduce the amount of refrigerant.

Max. additional charge for 1 outdoor unit

: 62 lbs

Max. additional charge for 2 outdoor units : 111 lbs

Max. additional charge for 3 outdoor units : 133 lbs

Unit: ft.