Sanyo R410A User Manual

Page 62

Advertising
background image

62

Fig. 5-4

Shielded wire

Ground

Ground

Fig. 5-5

Stranded wire

Ring
pressure
terminal

S

tr

ip

3

/8

i

n

.

Fig. 5-6

Wire

Special
washer

Screw

Ring pressure
terminal

Terminal plate

Screw and
Special washer

Ring
pressure
terminal

Wire

(5) Use shielded wires for inter-unit control wiring (c)

and ground the shield on both sides, otherwise

misoperation from noise may occur. (Fig. 5-4)

Connect wiring as shown in Section “5-3. Wiring

System Diagram.”

WARNING

Loose wiring may cause the

terminal to overheat or result

in unit malfunction. A fire

hazard may also exist.

Therefore, ensure that all

wiring is tightly connected.

When connecting each power wire to the terminal, follow

the instructions on “How to connect wiring to the terminal”

and fasten the wire securely with the fixing screw of the

terminal plate.

How to connect wiring to the terminal

For stranded wiring

(1) Cut the wire end with cutting pliers, then strip the

insulation to expose the stranded wiring about 3/8 in.

and tightly twist the wire ends. (Fig. 5-5)

(2) Using a Phillips head screwdriver, remove the terminal

screw(s) on the terminal plate.

(3) Using a ring connector fastener or pliers, securely

clamp each stripped wire end with a ring pressure

terminal.

(4) Place the ring pressure terminal, and replace and

tighten the removed terminal screw using a screwdriver.

(Fig. 5-6)

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 62

Advertising