3-2. Use R410A exclusive cylinder only.

Single-outlet valve

(with siphon tube)

Liquid refrigerant should be recharged

with the cylinder standing on end as

shown.

New refrigerant R410A cannot be used for
earlier models

1. Compressor specifications are different.

If recharging a R22 or R407C compressor with

R410A, durability will significantly decrease since

some of the materials used for compressor parts are

different.

2. Existing tubing cannot be used (especially R22).

Completely cleaning out residual refrigerating

machine oil is impossible, even by flushing.

3. Refrigerating machine oil differs (R22).

Since R22 refrigerating machine oil is mineral oil, it

does not dissolve in R410A. Therefore, refrigerating

machine oil discharged from the compressor can

cause compressor damage.

R22 refrigerating machine oil

Mineral oil (Suniso oil)

R407C refrigerating machine oil

Synthetic fluid (ether oil)

R410A refrigerating machine oil

Synthetic fluid (ether oil)