Installation site selection – Sanyo DC Inverter Split System XHS1271 User Manual

Page 89

Advertising
background image

4

1-5. Additional Materials Required for Installation

1.

Refrigeration (armored) tape

2.

Insulated staples or clamps for connecting wire

(See local codes)

3.

Putty

4.

Refrigeration lubricant

5.

Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

AVOID:

direct sunlight.

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

places where large amounts of oil mist exist.

DO:

select an appropriate position from which every corner of

the room can be uniformly cooled.

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the

shortest run to the outside.

allow room for operation and maintenance as well as unre-

stricted air flow around the unit. (Fig. 1)

install the unit within the maximum elevation difference (H)

above or below the outdoor unit and within a total tubing length

(L) from the outdoor unit as detailed in Table 3 and Fig. 2.

install the indoor unit more than 3.3' (1 m) away from any

antenna or power lines or connecting wires used for television,

radio, telephone, security system, or intercom. Electrical noise

from any of these sources may affect operation.

Fig. 1

3.3 ft.

(1m)

(1m)

(1m)

3.3 ft.

(1m)

3.3 ft.

3.3 ft.

3.3 ft.

(1m)

Fig. 2

Tubing length (L)

Elevation difference (H)

Outdoor unit

Indoor unit

WARNING

To prevent abnormal heat genera-

tion and the possibility of fire, do

not place obstacles, enclosures

and grilles in front of or surround-

ing the air conditioner in a way

that may block air flow.

CAUTION

Air delivery will be degraded if the distance

from the floor to the ceiling is greater than

10 ft. (3 m).

* If total tubing length becomes 25 to 65 ft. (Max.) or 25 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.16 or 0.27 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Model

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

(ft.)

(ft.)

(ft.)

(oz./ft.)

*

XHS1271

25

65

23

0.16

XHS1872

25

98

50

0.27

Table 3

08-193 XHS1271 9/12/08 2:58 PM Page 4