2-2. Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 3)

damp, humid or uneven locations.

DO:

choose a place as cool as possible.

choose a place that is well ventilated.

install in a location where at least two sides are unob-

structed, so that the flow of air at the intake port or

exhaust port is not blocked, and so that sufficient

space is ensured for maintenance to be carried out

without trouble. In general the top also must be unob-

structed. (Figs. 4a and 4b)

provide a solid base (level concrete pad, concrete

block, 4"

Ч 1'4" (10 Ч 40 cm) beams or equal), a mini-

mum of 4" (10 cm) above ground level to reduce

humidity and protect the unit against possible water

damage and decreased service life. (Figs. 5a and 5b)

Outdoor unit

Hot air

Heat source

Exhaust fan

NO

Fig. 3

Air intake

Min. 2" (5 cm)

Air discharge

Min.

2" (5 cm)

Min.
8" (20 cm)

Valve
side
Min. 10"
(25 cm)

Min.

7' (2 m)

Min.

7' (2 m)

Ground

Ob

s

tacle

Obstacle above

Air di

s

char

g

e

Min. 2" (5 cm)

Air intake

Air intake

Concrete
or equal

Abo

ut 4" (10 cm)

Min. 4" (10 cm)

Anchor bolts
(4 pcs.)

Abo

ut 1

'4" (40 cm)

Cushion rubber

Fig. 5a

Drain holes

CAUTION

A solid base must not cover

the hole of the bottom plate.

Fig. 4a

Air intake

Min. 4" (10 cm)

Air discharge

Min.

2" (5 cm)

Min.
1'4" (40 cm)

Valve
side
Min. 10"
(25 cm)

Min.

7' (2 m)

Min.

7' (2 m)

Ground

Ob

s

tacle

Obstacle above

Air di

s

char

g

e

Min. 4" (10 cm)

Air intake

Fig. 4b

(CH1872)

(CH1271)

install cushion rubber under unit’s feet to reduce vibra-

tion and noise. (Fig. 5c)

use lug bolts or equal to bolt down unit, reducing vibra-

tion and noise.

install in a location where no antenna of a television or

radio exists within 10' (3 m).

Fig. 5b

Fig. 5c