How to install the indoor unit, Fig. 6-1, Fig. 6-4 fig. 6-2 – Sanyo DC Inverter Split System XHS1271 User Manual

Page 91: Fig. 6-3

Advertising
background image

Hole-in-anchor

Concrete

Insert

Suspension bolt (M10 or 3/8")

Hole-in-plug

(locally purchased)

Fig. 6-1

23-5/8"(600mm)

21-1/32"(534mm)

Ceiling opening dimensions

Suspension bolt pitch

2

3

-5/

8

"(600

mm

)

21-1/

3

2"(5

3

4

mm

)

Ceili

ng

ope

n

ing

dime

ns

io

ns

Sus

pe

ns

io

n

bolt pitch

Drain tube
connection port

22-5/8"(575mm)

6-11/16"

(170mm)

(160mm)

(53mm)

6-5/16"

2-3/32"

(45

mm

)

1-25/

3

2"

(45

mm

)

1-25/

3

2"

(117

mm

)

4-19/

3

2"

Refrigerant tubing joint
(narrow tube side)

Power supply port

1-

3

/16"

(3

0

mm

)

(215

mm

)

8

-15/

3

2"

11-5/

3

2"(2

83

mm

)

(outer dia 1-1/32"( 26mm))

1/4( 6.35mm) (flared)

1/2" — 23/32" (13~18

mm

)

Over 19/32" (15

mm

)

Supplied screw

Full-scale installation diagram
(printed on top of container box)

3. How to Install the Indoor Unit

3-1. Preparation for Suspending

This unit uses a drain pump. Use a carpenter’s level to

check that the unit is level.

3-2. Suspending the Indoor Unit

(1) Fix the suspension bolts securely in the ceiling using

the method shown in the diagrams, by attaching

them to the ceiling support structure, or by any other

method that ensures that the unit will be securely

and safely suspended. (Fig. 6-1)

(2) Follow the diagram to make the holes in the ceiling.

(3) Determine the pitch of the suspension bolts using

the supplied full-scale installation diagram. The dia-

gram shows the relationship between the positions

of the suspension fitting, unit, and panel. (Fig. 6-2)

3-3. Placing the Unit Inside the Ceiling

(1) Be sure to remove the fan protection (4pcs) for

transportation before hanging up the indoor unit.

(2) When placing the unit inside the ceiling, determine

the pitch of the suspension bolts using the supplied

full-scale installation diagram. (Fig. 6-3)

Tubing and wiring must be laid inside the ceiling

when suspending the unit. If the ceiling is already

constructed, lay the tubing and wiring into position

for connection to the unit before placing the unit

inside the ceiling.

(3) The length of suspension bolts must be appropriate

for a distance between the bottom of the bolt and the

bottom of the unit of more than 19/32" (15 mm) as

shown in the diagram. (Fig. 6-3)

(4) Thread the 3 hexagonal nuts (locally purchased) and

2 supplied washers onto each of the 4 suspension

bolts as shown in the diagram. Use 1 nut and 1

washer for the upper side, and 2 nuts and 1 washer

for the lower side, so that the unit will not fall off the

suspension lugs. (Fig. 6-4)

(5) Adjust so that the distance between the unit and the

ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).

Tighten the nuts on the upper side and lower side of

the suspension lug. (Fig. 6-4)

Nuts and washers
(used for upper and lower)

Double nut

Notch

Suspension lug

Suspension bolt

1/2" — 23/32"

(13~18mm)

Fig. 6-4

Fig. 6-2

6

Fig. 6-3

08-193 XHS1271 9/12/08 2:58 PM Page 6