TP-6069 6/03

67

Section 8 Reconnection/Adjustments

Section 8 Reconnection/Adjustments

8.1 Four-Lead Reconnection

The following information illustrates the reconnection of
four-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).

NOTICE

Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.

8.1.1

100--120-Volt Configurations

If the installation requires a factory two-pole circuit
breaker, do not connect the load-side terminals of the
circuit breaker together; see Figure 8-1.

If the

installation requires a 100--120-volt, 2-wire system, use
a single-pole circuit breaker. See Figure 8-2. When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the

line side of the circuit breaker to balance the load of

the generator set.

GRD.

L1

L2

4

3

2

1

L0 (Neutral)

L0

Ground

Load
Side

Line
Side

Two-Pole
Circuit
Breaker

Jumper
lead

Figure 8-1

100--120-Volt, 3-Wire Configuration

8.1.2

100--120/200--240-Volt
Configurations

The 100--120/200--240-volt configuration does not use
a jumper lead. If the unit was originally wired for straight
100--120 volt, 3-wire, remove the jumper lead (see
Figure 8-1 for location).

Select a two-pole circuit

breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200--240-volt

load,

even

if

the

breakers

are

mechanically attached together. Leads L1 and L2 are
for different phases;

never connect them together.

4

3

2

1

Stator Leads

L0

GRD.

L1

L0 (Neutral)

Line
Side

Single-Pole
Circuit
Breaker

Ground

Load
Side

60 Hz

50 Hz

L0--L1

100--120 Volt

100--120 Volt

L0--L2

100--120 Volt

100--120 Volt

Figure 8-2

100--120-Volt, 2-Wire Configuration

4

3

2

1

Stator Leads

L0

GRD.

L2

L1

L0 (Neutral)

Line
Side

Factory
Two-Pole
Circuit
Breaker

Ground

Load
Side

100--120/200--240-Volt,
3-Wire

60 Hz

50 Hz

L0--L1

100--120 Volt

100--120 Volt

L0--L2

100--120 Volt

100--120 Volt

L1--L2

200--240 Volt

200--240 Volt

Figure 8-3

100--120/200--240-Volt, 3-Wire
Configuration