Figure 8-7 voltage adjustment, Lamp jumper, Output voltage adjustment potentiometer – Kohler Marine Generator Sets 11EFOZ/13EOZ User Manual

Page 79

Advertising
background image

TP-6069 6/03

69

Section 8 Reconnection/Adjustments

Note: Position the current transformers with the

dot or HI side CT marking toward the
generator set.

Note: Only generator sets equipped with AC meter

controllers

and/or

safeguard

circuit

breakers require CTs.

5. If the controller has meters, remove the controller

cover and reposition the meter scale lamp jumper
(see Figure 8-6) matching the position of the
desired voltage (shown in Figure 8-5).

TP-5353-6

1

1. Lamp Jumper

Figure 8-6

Meter Scale Lamp Jumper

6. The

overvoltage

shutdown

is

standard

on

Decision-Maker

t 3+

controllers.

The

139/240-volt (low wye) and 277/480-volt (high
wye), 3-phase, 4-wire, 60 Hz configurations use
different overvoltage shutdown settings than all
other configurations. Recalibrate the overvoltage
shutdown if the reconnection changes the voltage
to or from one of these configurations.

See

Section 8.3,

Decision-Maker

3+

Controller,

Overvoltage Shutdown Adjustment.

Do not

recalibrate the overvoltage adjustment for other
voltage changes.

7. If the controller has meters, set the phase selector

switch to the L1-L2 position (1-phase or 3-phase
configuration

depending

on

generator

set

connection). Connect a voltmeter across leads L1
and L2 if the controller has no meters.

Note: Equipment damage. Verify that the voltage

ratings of the transfer switch, line circuit
breakers, and other accessories match the
desired line voltage.

8. Reconnect the starting battery, negative (--) lead

last. Place the generator set master switch in the
RUN position to start the generator set. Observe
the voltmeter and verify that the unit has the
desired line voltage connection.

Adjust the voltage using the voltage adjustment
potentiometer on the generator controller front
panel. See Figure 8-7.

9. Stop the generator set after completing the voltage

adjustment.

10. Disconnect the external voltmeter if used. Replace

the controller cover.

ADV-5849A-

1

1. Output voltage adjustment potentiometer

EMERGENCY

STOP

ONLY

OFF/RESET

PREALARM

HIGH ENGINE

TEMPERATURE
PREALARM

LOW OIL

PRESSURE

LOW WATER

TEMPERATURE

LOW FUEL

HIGH ENGINE

TEMPERATURE

LOW OIL

PRESSURE

EMERGENCY

STOP

OVERSPEED

AUXILIARY

FAULT

BATTERY

CHARGER FAULT

LOW BATTERY

VOLTAGE

OVERCRANK

AUXILIARY

PREALARM

AIR

DAMPER

SYSTEM

READY

GENERATOR

SWITCH

NOT IN AUTO

NORMAL

SILENCE

LAMP

TEST

ALARM

AUTO

RUN

HERTZ

A--C VOLTS

A--C AMPERES

BATTERY

WATER

TEMP

OIL

PRESS

0 0 0 0 0

TOTAL HOURS

LOWER METER SCALES

3

OFF

1

UPPER METER SCALES

AMPS

VOLTS

L0--L1

L3

L3--L1

L2

L1--L2

L1

L1--L2

L1

L1--L2

L2

L2--L3

S

VOLTAGE

ADJUST

O

Figure 8-7

Voltage Adjustment

This is bpid

8.3 Decision-Maker 3+ Controller,

Overvoltage Shutdown
Adjustment

Disconnecting the electrical load. Hazardous voltage can
cause severe injury or death. Disconnect the generator set
from the load by opening the line circuit breaker or by
disconnecting the generator set output leads from the transfer
switch and heavily taping the ends of the leads. High voltage
transferred to the load during testing may cause personal
injury and equipment damage. Do not use the safeguard
circuit breaker in place of the line circuit breaker.

The

safeguard circuit breaker does not disconnect the generator
set from the load.

Advertising