Section 8 Reconnection/Adjustments
8.1.3
200--240-Volt Configurations
The 200--240-volt configuration does not use a jumper
lead. If the unit was originally wired for straight 100--120
volt, 3-wire, remove the jumper lead (see Figure 8-1 for
location).
4
3
2
1
Stator Leads
L0
GRD.
L1
L0 (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
200--220--240 Volt
2 Wire
Tape to insulate
from ground
60 Hz
L0--L1
200-240 Volt 200--220--240 Volt
50 Hz
Figure 8-4
200--220--240-Volt, 2-Wire Configuration
8.2 Twelve-Lead Reconnection
The
reconnection
procedure
details
voltage
reconnections only.
If the generator set requires
frequency changes, adjust the governor and voltage
regulator. See the generator set service manual for
information regarding frequency adjustment.
The following information illustrates the reconnection of
twelve-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
Reconnect the stator leads of the generator set to
change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
precautions at the front of this manual and in the text
during the reconnection procedure.
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
Twelve-Lead Reconnection Procedure
1. Place the generator start/stop switch in the STOP
position.
2. Disconnect generator set engine starting battery,
negative (--) lead first.
3. Disconnect power to battery charger, if equipped.
4. Use Figure 8-5 to determine the generator set
voltage configuration.
Note the original voltage
and reconnect the generator set as needed. Route
leads through current transformers (CTs) and
connect the leads according to the diagram for the
desired phase and voltage.
EM-250000-E
Note:
Current Transformers (CTs) are not used on all sets. CT dot or “HI” toward generator.
Figure 8-5
Generator Reconnection
- Marine Generator Sets 4EFOZ/5EOZ Marine Generator Sets 20EFOZ/24EOZ Marine Generator Sets 40EFOZ/50EOZ Marine Generator Sets 3.5EFOZ/4EOZ Marine Generator Sets 23EFOZ/28EOZ Marine Generator Sets 19EFOZ/23EOZ Marine Generator Sets 11.5EFOZ/14EOZ Marine Generator Sets 16EFOZ/20EOZ Marine Generator Sets 6.5EFOZ/8EOZ Marine Generator Sets 9EFOZ/10EOZ Marine Generator Sets 8.5EFOZ Marine Generator Sets 17.5EFOZ/20EOZ Marine Generator Sets 100EFOZ/125EOZ Marine Generator Sets 80EFOZ/99EOZ Marine Generator Sets 13EFOZ/15.5EOZ Marine Generator Sets 125EFOZ/150EOZ Marine Generator Sets 33EFOZ/40EOZ Marine Generator Sets 27EFOZ/32EOZ Marine Generator Sets 55EFOZ/65EOZ