TP-6069 6/03

68

Section 8 Reconnection/Adjustments

8.1.3

200--240-Volt Configurations

The 200--240-volt configuration does not use a jumper
lead. If the unit was originally wired for straight 100--120
volt, 3-wire, remove the jumper lead (see Figure 8-1 for
location).

4

3

2

1

Stator Leads

L0

GRD.

L1

L0 (Neutral)

Line
Side

Single-Pole
Circuit
Breaker

Ground

Load
Side

200--220--240 Volt
2 Wire

Tape to insulate
from ground

60 Hz

L0--L1

200-240 Volt 200--220--240 Volt

50 Hz

Figure 8-4

200--220--240-Volt, 2-Wire Configuration

8.2 Twelve-Lead Reconnection

The

reconnection

procedure

details

voltage

reconnections only.

If the generator set requires

frequency changes, adjust the governor and voltage

regulator. See the generator set service manual for
information regarding frequency adjustment.

The following information illustrates the reconnection of
twelve-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).

Reconnect the stator leads of the generator set to
change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
precautions at the front of this manual and in the text
during the reconnection procedure.

NOTICE

Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.

Twelve-Lead Reconnection Procedure

1. Place the generator start/stop switch in the STOP

position.

2. Disconnect generator set engine starting battery,

negative (--) lead first.

3. Disconnect power to battery charger, if equipped.

4. Use Figure 8-5 to determine the generator set

voltage configuration.

Note the original voltage

and reconnect the generator set as needed. Route
leads through current transformers (CTs) and
connect the leads according to the diagram for the
desired phase and voltage.

EM-250000-E

Note:

Current Transformers (CTs) are not used on all sets. CT dot or “HI” toward generator.

Figure 8-5

Generator Reconnection