Appendix A Generator Selection and Wattage Requirements

Consider total wattage requirements (lights, motors,
appliances) when selecting a generator set or when
sizing wattage usage in which available space and
construction limit the size of the generator set.

Motors

When figuring generator set capacity requirements for
loads that include electric motors, consider the high
current demanded by the motors during startup. The
inrush or starting current is typically 2--3 times higher
than that required when the motor reaches normal
operating speed. Allow reserve for inrush demands plus
other loads which could be on the line as the electric
motor starts. Use Figure 1 as a guide when selecting
generator set capacity requirements involving motor
loads.

Motor

HP

Starting (Inrush)

Watts

Running

Watts

1/4

750

330

1/3

1000

400

1/2

1500

600

3/4

2000

750

1

3300

1100

2

4000

2000

3

5000

3000

Figure 1

Motor Requirements

Lighting

To calculate lighting load, add the wattage of each
generator set-operated lamp. Note that not all of the
lights or lamps are on the generator set AC circuit; some

are DC powered by a 12-volt battery. Make sure the
calculated total wattage includes only lights actually on
the generator set AC circuit.

Air Conditioners

The starting characteristics of air conditioners vary
greatly; one 12,000 Btu unit has, for example, lower
starting requirements than a 10,000 Btu unit of another
variety. When using only one unit, there is usually no
starting problem, provided the lighting and appliance
load is not too high when starting the unit.

Simultaneous starting of two air conditioning units,
however, can present problems if the generator set
capacity is marginal. Because of the variation in starting
characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
capabilities of the generator set covered. Consider
delayed starting or use of easy-starting devices on air
conditioner units whenever simultaneously starting
more than one motor.

See Figure 2 for typical air conditioner requirements.
Information will vary with manufacturer.

Appliances

Generator sets often furnish AC for appliances such as
TV, stereo, electric water heater, etc. With the exception
of the resistance-type loads such as the water heater,
requirements for appliances are usually low. Do not
overlook such loads when figuring total requirements.
Allow reserve capacity for anticipated appliance loads to
avoid overloading a generator set.

Air Conditioner Size (Btu/Hr.)

7,000

9,000

12,000

16,000

24,000

Voltage

115

230

115

230

115

230

115

230

230

Full load amps

9.3

4.8

9.9

5.0

11.8

6.3

16.3

8.0

11.6

Rated load amps

7.7

4.0

7.0

3.5

8.9

4.8

13.0

6.2

10.2

Locked rotor amps

34.0

20.0

40.0

20.0

50.0

31.0

75.0

36.0

56.0

Starting (inrush) watts

3910

4600

4600

4600

5750

7130

8630

8280

12,900

Running watts

886

920

805

805

1020

1100

1500

1430

2350

Figure 2