A-4 Appendix

Appendix C Generator Set Output Ratings Procedure

Kohler Co. develops the kilowatt output rating of a Kohler

r

marine generator set based upon the calculations
specified in ISO 3046 and ISO 8528-1. The calculations
correct for environmental variables encountered in a

generator

set

installation.

Figure 1

outlines

the

calculations.

Figure 2 contains examples of how heat

variables affect generator set ratings.

Generator Output

corrected

= Generator Output

observed

x Correction Factor

Output power is expected to be within

±5% of the specified rating when corrected to reference conditions.

Correction factors are determined using the following formulas:

1.

For naturally aspirated compression-ignition engines (power limited by excess air):
C.F. = [1.175 (29.2 / Dry Barometer in. Hg)

1

(Temperature

_F + 460/537)

.75

-- .175]

x Alternator Efficiency

Reference

/ Alternator Efficiency

Observed

2.

For turbocharged compression ignition engines:
C.F. = [1.175 (29.2 / Barometer

Observed

in. Hg)

.7

(Temperature

_F + 460/537)

2

-- .175]

x Alternator Efficiency

Reference

/ Alternator Efficiency

Observed

3.

For turbocharged and intercooled compression ignition engines:
C.F. = [1.175 (29.2 / Barometer

Observed

in. Hg)

.7

(Temperature

_F + 460/537)

1.2

-- .175]

x Alternator Efficiency

Reference

/ Alternator Efficiency

Observed

Reference conditions:

Temperature: 77

_F; Pressure: 29.2 in. Hg dry barometer.

Kohler sound shield increases ambient intake air approx. 12

_F

Approximate derates:

Temperature: approximately 1% per 10

_F (turbocharged engines have a greater derate);

Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg)

Figure 1 Generator Output

5.5

5.6

5.7

5.8

5.9

6.0

6.1

6.2

6.3

6.4

6.5

6.6

6.7

6.8

6.9

7.0

7.1

7.2

7.3

7.4

7.5

7.6

7.7

7.8

7.9

8.0

75

80

85

90

95

100

105

110

115

120

Temperature (

_F)

77

60 Hz
50 Hz

KEY

Figure 2 Example: 6.5EFOZ/8EOZ kW Derates (ISO 3046/ISO 8258-1)