Karcher WATERCLEAN 600 CD User Manual

Page 15

Advertising
background image

15

WTC 600 LP / MP

DESCRIPTION

Service Handbook 08.2004

2.3.1.7

Pressure-increase Pump

If required, the WTC 600 PI pressure-increase
pump (6/1) is connected between untreated
water supply and RO system. It is used for
pressure increase of the untreated water.

A pressure-increase pump should
be used for a water pressure (flow
pressure)

Յ

2 bar.

Observe mechanical protection as
well as protection of the
connection cable against water!

2.3.2

Safety Installations

Emergency Stop
The emergency stop switch (7/4) (main switch) is located on the side of the switch box.

RC Protective Switch
RC protective switch (external): i

Յ

30 mA

Circuit Breaker
Automatic circuit breaker (7/3) 10 A for power limitation of the power outlets, etc

Motor Protection Switch
The motor protection switch (7/2) is factory-set depending on the power consumption of the RO
pump (compare circuit diagram (7/1)) and must be checked:

WTC 600

Nominal output

Actual power

Motor protection

RO pump

consumption

switch setting

LP 400 V

2.2 kW

1.5 kW

4 A

MP 400 V

2.2 kW

2.2 kW

5.1 A

LP 230V

2.2 kW

1.5 kW

10 A

MP 230 V

2.2 kW

2.2 kW

14 A

Table 2

Setting of motor protection switch

Figure 6

WTC 600 PI

1

NOTE

CAUTION