4.5.4

Malfunctions – Media and Activated Carbon Filter, Fine Filter and Flocculation

Indication

Malfunction

Cause

Corrective Action

Chap./Fig.

More than one

Backwashing is

Load of debris

Install suitable preliminary 3.4.2.4

backwashing

initiated too often

too high

treatment; consultation

Tab. 24

per day

through sales

(diagnosis
controller)

Backwashing no

Pump defective

Replace pump or

sufficient

repair

Intake side of

Clean

pump clogged

Intake side of

Shorter line set-up;

pump too long

notify sales

Sand

Heavily soiled

Notify sales

conglutinated

water

Differential

Filtrate of the sand

Small particles

Install preliminary

4.1

pressure of

filter turbid

come through

treatment

fine filter quickly
exceeds 1 bar

Filtrate of the

Small particles

Check sand filter;

4.1

activated carbon

come through

install preliminary

filter turbid

treatment as required

Filter material

No backwashing Carry out backwashing;

3.4.2.1

conglutinated

carried out for too if without success,
long

replace sand

Too much

Reduce metering amount

flocculation agent of flocculation agent;
added

carry out backwashing

Indication of the

Power supply

Notify electrician

controller

disconnected

remains dark

Control wheel

Control switch or Replace controller

does not stand

switching

still

mechanism
defective

No changes of

Backwashing is

Controller

Change

3.4.2.4

the “back-

not initiated

incorrectly

programming

washing”

programmed

counter

Tabelle 31