Karcher WATERCLEAN 600 CD User Manual

Page 86

Advertising
background image

86

APPENDIX

WTC 600 LP / MP

Service Handbook 08.2004

4.4.1

Main menu

The details of the different menu points of the main menu are described below.

Menu point:

Function:

1 Ackn. failure

This menu point allows to acknowledge an operating failure
(the only possibility if ps acknowledgement = with password).

2 Operat. mode

This menu point allows to change the operating mode by means of a
selection. For safety purposes, selection only can be made between
STOP and OPERATION as well as STOP and DISINFECTION
respectively (direct change-over from OPERATION to DISINFECTION
is not possible).

2 Cy permeate

Permanent display of current permeate conductivity. To leave this menu
point press one of the keys.

4 Temp. permeate

Permanent display of current permeat temperature. To leave this menu

point press one of the keys.

5 Hour meter

Calling-in (display) of the operating hours meter.

6 Cy limits

Numerical entry of LIM and aaLIM.

7 Optional alarm

Setting (selection) of ps LIM high

8 Calibration

This menu point assures branching to the calibration menu (see item
4.4.3). The new calibration will be stored if the entered data are
acknowledged before leaving the calibration menu.

9 Setting

This menu point assures branching to the setting menu (see item 4.4.4).
The modification will be stored of the entered data are acknowledged
before leaving the setting menu.

10 Diagnosis

This menu point assures branching to the diagnosis menu (see item
4.4.5). At the beginning of the diagnosis, all actuators of the unit are
switched off. The sytem returns to the previous status if diagnosis is
completed.