Chapter 2 Installation 11

E1-20010329-C-1.0

Figure 2-4 rear panel

2.2.2 Front Panel

Parts' Function Description

Input Switch

Used for controlling the utility input to UPS.
10kVA UPS uses three-pole 63A/250VAC breaker
15/20kVA UPS uses three-pole 100A/250VAC breaker

Bypass Switch

Used for controlling the bypass input to UPS
10kVA UPS uses 80A/250VAC circuit breaker;
15/20kVA UPS uses 125A/250VAC circuit breaker

Maintenance
switch

For switching UPS to maintenance bypass.
Note: To be operated by trained technical Personnel only.

Front Panel air
inlet hole

for ventilation of UPS

LCD Panel and Description is in Appendix 1 in detail.

2.2.3 Rear Panel

Parts' Function Description

Input/output
terminals

Used for UPS input/output cable connection and
external battery connection for UPS

Contact closure port Provide Optical Coupler Dry Contact control

signal, for OS and UPS shutdown.


Alarm relay port


bProvide relay Dry Contact alarm/ control signal,

contact closure port

Alarm Relay Port

Ventilation holes

Input/Output Terminals block