40 Appendix 3 Product Specification

E1-20010329-C-1.0

Capacity 10kVA

15kVA

20kVA

Model GXT2-3X1

-0100L

GXT2-3X1
-0150L

GXT2-3X1 -0200L

Bypass Voltage

120~253Vac (non- ECO mode)

Efficiency in
Normal Mode
(100% Linear
Load)

> 89%

> 89%

> 89%

Efficiency in
battery mode
(100% Linear
Load)

> 88%

> 88%

> 88%

interrupt
time

Utility Failure

0ms

Transferring
between inverter
and Bypass

Synchronized )

< 4ms

Voltage transient response At the Resistive Load from 0~100% or 100%~0, the Output dynamic

voltage change range is lower than 5% Rated Voltage. Transient recovery
time is less than 60ms.

Audible Noise

< 55dB(1m) <

60dB(2m)

Display LCD
Safety

Passed CCEE certification,complied with EN60950 and EN50091-1.

Highest Input Voltage :

Line Voltage 554Vac,1 hour(static)

EMC Conduction:EN55022

Class

A

Radiation: EN55022 Class A
Harmonic current:THD<25%(With input isolated transformer connected)

Immunity

EN61000-4-2.3.4.5.6.8.11 Level III

DC offset

Lower than ±500mVdc

MTBF(Inverter )

30000 hours (ambient temperature is 25℃,rated condition)

MTBF(System)

150000 hours (Response time + maintenance time should be less than 24
hours)

MTTR (Board Maintenance) 1 hour(Board Maintenance)
Insulation Resistance

> 2MW (500Vdc)

dielectric Strength

Output to earth,Input to earth )2820Vdc,leakage current<3.5mA, 1min

with no arc and breakdown

Surge Protection

Satisfy the IV type of IEC60664-1, that is the ability to withstand
1.2/50uS+8/20uS exceeds 6kV/3kA.

Protection Level

IP21