Relay communication mode – Liebert GXT2 - 3X1 User Manual

Page 37

Advertising
background image

Appendix 2 Communication Port Description 37

E1-20010329-C-1.0

Dry Contact Communication Mode

Port Definition

Pin2 : When the Utility fails, this pin will change from OPEN to CLOSE, it is OPEN in normal state;
Pin5 : When the battery voltage is low, this pin will change from OPEN to CLOSE, it is OPEN in normal state;
Pin6 : When +5V voltage has been applied for 1 second, the UPS will shutdown;
Pin4 : GND for signal;
Pin7 : GND for signal;
Other Pin: No wire connection

Dry Contact Communication Mode can perform the following functions

When the Utility fails, the Utility failure information is provided ;

When the battery capacity is going to be used up, battery low information will be
provided ;

Control the shutdown of UPS.

Relay Communication Mode

Port Definition

Signal

alarm

Output signal , summary alarm , non shutdown
alarms only.

failure

Output signal UPS fail , will shutdown or transfer to
bypass.

Bypass

Output signal, power supplying mode

battery low

Output signal, battery mode

shutdown

input signal, UPS shutdown command

NC

Utility Fail

NC

GND

Battery Undervolt

OFF

GND

NC
NC

1
2
3
4
5

6
7
8
9

ALARM

FAULT

BYPASS

BATT ¡ ¤

LOW

SHUTDOWN

1 2

3

4 5 6

7 8

9

10 11 12

13 14 15