Chapter 5 Handling Abnormal Problem 29

E1-20010329-C-1.0

Chapter 5 Troubleshooting

In the event of UPS fault, please check and remove the fault immediately following the
methods described in the table below. If the fault persist , please contact Liebert or its
authoriged agents.

Sequence

No.

Phenomena

Description

Cause Action

1

No panel display and
system self-test when
the Utility switch is in
the ON position.

A. Utility hasn't been
introduced into the
system;
B. Input undervoltage.

Use voltmeter to check
whether the input Utility
voltage is within
tolerances.

2

The Utility is normal,
but the Utility indicator
does not turn to and
the UPS operates in
Battery mode.

A. The input switch is
turned off;
B. The input power line
is not properly
connected;

A. Turn on the input
switch;
B. Make sure that the
input power line is
properly connected;

3

No alarm is given, but
there is no voltage
output.

The output power line is
not properly connected.

Make sure that the output
power line is properly
connected.

4

No panel display and
system self-test when
the Utility switch is in
the ON position.

A. Utility hasn't been
introduced into the
system;
B. Input undervoltage.

Use voltmeter to check
whether the input Utility
voltage is within
tolerances.

5 The

Utility

indicator

flashes.

The Utility voltage is
outside tolerances.

If the UPS is operating in
Battery mode, please
note the battery backup
time.

6 The

buzzer

beeps

every 0.5 second, and

the LCD displays

"OVERLOAD"

Overload.

Disconnect some loads
from the UPS.

7

The fault indicator is on

and the LCD displays

"BATTERY FAIL".

A. The external battery

switch is turned off, or

its lead is not properly

connected;

B. Battery reverse

connection;

C. Battery damaged;

A. Check whether the
external battery switch is
turned on and its lead is
properly connected;
B. Check whether the
battery is reversely
connected;
C. Contact the distributor
for battery replacement;

8

The fault indicator is
on , and the LCD
displays "CHARGER
FAIL".

Charger fault

Contact the Liebert or its
authoriged agent for
charger
replacement/maintenanc
e.

Advertising