38 Appendix 2 Communication Port Description

E1-20010329-C-1.0

Connection

alarm Signal

Pin . 1/2/3 (normally open /common
normally close)

failure Signal

Pin . 4/5/6 (normally open/common
/normally close)

Bypass mode signal

Pin . 7/8/9 (normally open/common
/normally close)

battery low Signal

Pin . 10/11/12 (normally open/
common / normally close)

Shutdown Signal

Pin .14/15th Pin(short circuited
normally , UPS shutdown when open
circuit )

Connection of relays

alarm Signal Relay

In normal state, Pin . 2/3 are short
circuited, Pin . 1/2 pins are short
circuited when alarm is activated .

failure Signal Relay

In normal state, Pin . 5/6 are short
circuited, No. 4/5 pins are short
circuited when signal is activated.

Bypass mode Signal Relay

In normal state, Pin . 8/9 are short
circuited, Pin .7/8 are short circuited
when signal is activated.

battery low Signal Relay

In normal state, Pin . 11/12 are short
circuited_, Pin . 10/11 are short
circuited when signal is activated .

Shutdown Signal Relay

Invalid when pin 14/15 are open
circuit , UPS will shutdown .

Relay Contact Capacity

250VAC 2A or 30VDC 2A