Liebert iCOM Microprocessor TM-10098 User Manual

Page 104

Advertising
background image

iCOM

Control Training and Service Manual

iCOM Control Board DIP Switch #2 Settings

Connector

Input/ Output Type

Setting

P7-1 (+)/ P7-2 (-)

NTC Thermistor

* Software (ASW1 = 1)

PTC Thermistor

Software (ASW1 = 0)

P11-1 (+)/ P11-2 (-)

Analog Voltage: 0 to +10V

* Sw2-1: Off/ Sw2-2: Off

Analog Voltage: 0 to +5V

Sw2-1: On/ Sw2-2: Off

Analog Current: 4 to 20mA

Sw2-1: On/ Sw2-2: On

P11-3 (+)/ P11-4 (-)

+5V Output

None

P11-5 (+)/ P11-6 (-)

Analog Voltage: 0 to +10V

* Sw2-3: Off/ Sw2-4: Off

Analog Voltage: 0 to +5V

Sw2-3: On/ Sw2-4: Off

Analog Current: 4 to 20mA

Sw2-3: On/ Sw2-4: On

P11-7 (+)/ P11-8 (-)

+5V Output

None

P12-1 (+)/ P12-2 (-)

Analog Voltage: 0 to +10V

* Sw2-5: Off/ Sw2-6: Off

Analog Voltage: 0 to +5V

Sw2-5: On/ Sw2-6: Off

Analog Current: 4 to 20mA

Sw2-5: On/ Sw2-6: On

P12-3 (+)/ P12-4 (-)

+5V Output

None

P12-5 (+)/ P12-6 (-)

Analog Voltage: 0 to +10V

* Sw2-7: Off/ Sw2-8: Off

Analog Voltage: 0 to +5V

Sw2-7: On/ Sw2-8: Off

Analog Current: 4 to 20mA

Sw2-7: On/ Sw2-8: On

P12-7 (+)/ P12-8 (-)

+5V Output

None

P13-1 (+)/ P13-2 (-)

NTC Thermistor

* Software (ASW2 = 1)

PTC Thermistor

Software (ASW2 = 0)

P13-3 (+)/ P13-4 (-)

NTC Thermistor Sw2-9:

On

NTC Scroll Thermister

* Sw2-9: Off

P13-5 (+)/ P13-6 (-)

NTC Thermistor

Sw2-10: On

NTC Scroll Thermister

* Sw2-10: Off


* Default Setting