iCOM
Controls Training and Service Manual
Service Menu: Set Point Parameters S100 series: Page 2 of 2
Menu Line
Parameter
Default
Range
S112 Password
-
-
S113
Humidity Proportional Band
10%
1 – 20%
S114
Humidity Integration Time
0
0 – 5 minutes
S115
Humidity Deadband
0
0 – 50%
S116
DT Between Room / FC Type
Disable
Disable, Contact,
Value
S117
DT Between Room Air / FC Fluid
8ºF
0 - 36ºF
S118
Minimum CW Temp
Disable
Enable / Disable
S119
Minimum CW Temp Value
45ºF
32 - 68ºF
S120
S121
S122
Service Menu: Unit Diary Log
Parameter
Displays changes to the unit as performed and entered by
the service person or customer