Events notifications parameters (continued), Event id number, description and function – Liebert iCOM Microprocessor TM-10098 User Manual

Page 93

Advertising
background image

iCOM

Controls Training and Service Manual

Events Notifications Parameters (continued)

ID

Type

Description (Large Display)

Description (Small Display)

111 Warning

EL.HEAT 1 HOURS

EXCEEDED

EL.HEAT 1 HOURS EXC.

112 Warning

EL.HEAT 2 HOURS

EXCEEDED

EL.HEAT 2 HOURS EXC.

113 Warning

EL.HEAT 3 HOURS

EXCEEDED

EL.HEAT 3 HOURS EXC.

Event ID number, Description and Function

ID Description

Event explanation

Default

Type

Shut

down

single

unit

Rotat

e

stand

by

restart if

duty unit

fails also

000 GENERAL

ALARM

Warning or Alarm was
acknowledged or reset

Reset - -

-

001 COMP 1 HIGH

PRESSURE

Compressor 1 stopped
because of high pressure

Alarm

no

yes

yes

(broken co
will remain

off)

002 COMP 1 LOW

PRESSURE

Compressor 1 stopped
because of low pressure

Alarm no yes yes

(broken co
will remain

off)

003 HIGH CW

TEMP

chilled water temperature
too high (input from
thermostat)

Warning

no

no

-

004 LOSS OF CW

FLOW

chilled water flow too low
(input from flow switch)

Warning

no no

-

005 EL HEAT HIGH

TEMP

electric heaters stopped
because of too high
temperature on the
safety thermostat

Warning

no

no

-

006 MAIN FAN

OVERLOAD

fan motor protection has
stopped the fan due to
overload.
this event can be set to
switch off the unit or to
disable hum and electric
heat.

Alarm yes,

if

set to

shut

down

yes

yes, only if

set to

"disable"

92